Thermography Study of Electrical Systems

Client electrical installations

131 °C
Highest recorded hot spot
Detected before failure
Failure risk

Challenge

The brief

Loose terminations and overloaded components fail without warning, causing fire risk and unplanned outages that routine visual inspection does not catch.

Assessment

What we did

Infrared thermography was performed on live electrical panels, MCCBs, busbars, cable terminations and switchgear, with camera and thermal images recorded side by side for each observation.

Findings

What the data showed

  • Localised overheating at terminations and joints requiring immediate attention
  • Component-level temperature rise indicating loading or contact resistance issues

Recommendations

What we recommended

  • Prioritised corrective action on identified hot spots
  • Torque and contact resistance checks during planned shutdown
  • Periodic thermography as part of the electrical maintenance regime